Your generator runs fine on light work. Then you add the welder or the second pump, and the breaker trips. You reset it, load it up again, and it trips again.
A trip is the generator protecting itself and your equipment. The job is to find out which protection is acting and why. This guide covers the common causes, the generator parts involved, and the generator servicing that stops repeat trips on Australian farms, homes and work sites.
Generator: How Does It Work?
Before chasing faults, it helps to know the basics. So, generator: how does it work?
- Engine: Burns diesel or petrol and spins a shaft at a fixed speed, usually 3,000 or 1,500 rpm for 50 Hz power in Australia
- Alternator: Turns that spinning motion into electricity
- Automatic voltage regulator (AVR): Holds output at 230 V single phase or 400 V three phase as the load changes
- Governor: Adds fuel as the load rises to keep the engine speed steady
- Circuit breaker and RCD: Cut power when current runs too high or leaks to earth
- Engine sensors: Shut the engine down on high temperature or low oil pressure
When you ask “generator, how does it work under heavy load?”, the answer is simple. The engine needs more fuel, the alternator carries more current, and everything runs hotter. Any weak point shows up here first.
Which Trip Are You Getting?
Different trips point to different problems. Note what happens before you reset anything.
| What you see | Protection acting | Likely cause |
| Breaker trips, engine keeps running | Overcurrent breaker | Overload or starting surge |
| Power cuts instantly, often with wet tools | RCD | Earth leakage from damaged leads or tools |
| Engine stops, warning light on | Low oil pressure sensor | Low oil or faulty sensor |
| Engine stops after long heavy running | High temperature switch | Cooling problem |
| Output drops out, engine hunting | Over/under frequency or voltage protection | Governor or AVR fault |
Common Causes of Tripping Under Load
The following are some caues
1. Plain overloading
Most generators handle their full rated output for short periods only. Keep continuous load at around 80 per cent of the rating. A 10 kVA unit shouldn’t carry much more than 8 kVA all day.
2. Starting surges
Motors in pumps, compressors and fridges draw 3 to 7 times their running current as they start. Several starting together can push the breaker past its limit. Start the largest motor first and bring others on 5 to 10 seconds apart.
3. Earth leakage
Cut leads, water in plugs and worn tool insulation all leak current to earth. The RCD sees this and trips. In Australia, AS/NZS 3012 requires RCD protection for electrical equipment on construction and demolition sites, and AS/NZS 3760 covers inspection and testing of leads and tools. Test and tag your leads on schedule.
4. Unbalanced three-phase loads
On a three-phase commercial generator, piling single-phase loads on one phase overloads that phase while the others sit idle. The breaker trips even though total output looks fine. Spread loads evenly and aim to keep phases within about 10 per cent of each other.
5. Heat
A hot engine or alternator loses capacity, and breakers trip at lower currents when they run hot. Blocked radiators, low coolant and poor airflow are common culprits. Our guide on diesel generator overheating covers the cooling checks in detail.
6. Worn generator parts
Breakers weaken with age, sensors drift and AVRs fail. A worn part can trip at loads the machine handled easily last year.
Quick Checks Before You Call a Technician
With the generator off and cool:
- Add up the running watts of everything connected and compare with the rated output
- Inspect every lead and plug for cuts, crushed sections and moisture
- Unplug all loads, start the generator and reconnect items one at a time to find the one that trips it
- Check oil and coolant levels
- Clear dust, grass and debris from air intakes and the radiator
- Check the air filter and fuel filter for blockages
If the breaker trips with nothing connected, stop there. That points to an internal fault, and a licensed electrician or generator technician needs to inspect it.
Generator Parts That Cause Trips
| Generator parts | Warning sign | Typical check |
| Circuit breaker | Trips below its rating, feels hot | Test at each service |
| RCD | Trips with no load connected | Push-button test monthly |
| AVR | Voltage swings, lights flicker | Test output voltage at service |
| Oil pressure sensor | Shutdowns with oil level correct | Test or replace if faulty |
| Air and fuel filters | Engine bogs, black smoke | Clean or replace per manual |
| Radiator and fan belt | Temperature climbs under load | Inspect every service |
Always use generator parts matched to your model. A breaker with the wrong rating either trips too early or, worse, doesn’t trip when it should.
Generator Servicing That Prevents Trips
Regular generator servicing catches most trip causes before they stop your work. Follow your manual, but these intervals suit many small and mid-size diesel units:
- First 20 to 50 hours: First oil change after running in
- Every 50 hours: Clean air filter, check oil, coolant and belts
- Every 100 to 250 hours: Change oil and oil filter
- Every 250 to 500 hours: Replace fuel filter, drain water from the fuel system
- Every 12 to 24 months: Replace coolant, test breakers, RCD and AVR
Standby units that rarely run still need generator servicing. Start them monthly and run them under load for at least 30 minutes, as light running alone leaves carbon build-up in diesel engines.
Extra Checks for a Commercial Generator
A commercial generator powering a site, workshop or farm carries more risk when it trips. Add these to your routine:
- Load audit: List every machine, its running load and starting load, and update it when you add equipment
- Phase balancing: Measure current on each phase under normal working load
- Service logbook: Record hours, parts replaced and trip events so patterns show early
- Load bank testing: Test standby units at full load once a year
- Capacity review: If you regularly run above 80 per cent, move to a larger commercial generator or add a second unit
How Thornado Can Help?
Thornado supplies generators, pumps, hoses and fittings to businesses and households across Australia. If your current unit keeps tripping because the load has outgrown it, look at our diesel generator range:
- 10kVA Silent Diesel Generator, Key Start, 3 Phase for three-phase sites and workshops
- 8.5kVA Silent Diesel Generator, Single Phase for farms, sheds and backup power
- 8.5kVA Inverter Generator, Trade Series for tradies running sensitive tools and electronics
Why buy from Thornado:
- 12 months warranty, with details in our warranty policy
- 30 days money back
- Free delivery on orders over $200 ex GST
- Trade accounts for approved businesses
- Sizing advice from our team in Ingleburn, NSW
Send us your equipment list, call (02) 9600 8883 or contact us, and we’ll help you match the right generator to your load.
Conclusion
A generator that keeps tripping under heavy load is usually overloaded, leaking to earth, running hot or overdue for attention. Identify the trip type, check your loads, and keep up regular generator servicing with the right generator parts. For a commercial generator, a load audit and phase check will often solve the problem for good.