You switch on the bore pump. The compressor kicks in a second later. The lights dim, the engine note drops and the breaker trips.
Your generator hasn’t failed. It simply can’t supply the surge that several motors demand at the same moment.
This guide explains why a generator or diesel generator loses power under combined start-up loads, how to fix it, and when generator paralleling or a generator’s transfer switch makes sense for Australian sites, farms and homes.
Starting Load vs Running Load
Every electric motor pulls far more current in its first second than it does once it reaches speed. Electricians call this inrush or starting current.
A 2.2 kW single-phase pump might run at around 10 amps, yet draw 50 to 60 amps as it starts. When three motors start together, your genset sees all those surges stacked on top of each other.
| Load type | Typical starting demand |
| Heaters, kettles, lights | About 1 times running load |
| Handheld power tools | Up to 2 times |
| Pumps and fans (induction motors) | 3 to 7 times |
| Air compressors and fridges | 4 to 7 times |
| Submersible bore pumps | Up to 7 times |
These are typical ranges. Always check the nameplate or the manual for your equipment.
If the combined surge goes past what the engine and alternator can deliver, voltage and frequency fall. That drop is the “power loss” you notice.
Signs Your Genset Is Struggling
- Lights dim or flicker when a motor starts
- Motors hum but won’t turn, or take several seconds to reach speed
- Engine revs sag and a diesel generator puffs black smoke
- Circuit breakers or overloads trip
- Computers, chargers and controllers reset or shut off
- The genset shuts down on overload or under-frequency protection
Common Causes and Fixes
| Cause | What’s happening | Fix |
| Undersized genset | Sized on running watts only | Re-size using starting load |
| Loads start together | Surges stack at the same moment | Stagger start-ups |
| Slow governor response | Engine can’t add fuel fast enough, so speed drops | Reduce block loads or upgrade to an electronic governor |
| Tired voltage regulator (AVR) | Voltage recovers slowly after a surge | Test and service the AVR |
| Fuel or air restriction | Blocked filters or water in diesel starve the engine | Stick to the service schedule |
| Long or thin leads | Voltage drops along the cable | Use shorter, heavier gauge leads |
| Little headroom | Running close to the rating already | Keep continuous load at 70 to 80 per cent |
Heat matters too. Output falls on hot days, and a 40°C afternoon in Western Sydney or the Pilbara can cut what your generator delivers. Check the derating chart in your manual.
How to Stop the Power Drop?
1. Stagger your start-ups
Start the biggest motor first. Wait 5 to 10 seconds, then bring on the next one. This simple habit solves most problems on a correctly sized diesel generator.
2. Size the genset properly
Use this quick method:
- Add up the running watts of every load
- Find the single largest starting load
- Add that starting figure to the running watts of everything else
- Add 20 to 25 per cent headroom
- Divide by 0.8 to convert kW to kVA, since most generators are rated at a 0.8 power factor
3. Fit soft starters or variable speed drives
A soft starter can cut motor inrush to around 2 to 4 times running current. A variable speed drive brings it down further.
4. Keep up the servicing
Change fuel and air filters, drain water from the fuel system and test the battery. Overheating can also cut output, so read our guide on keeping your diesel generator from overheating.
Generator Paralleling: When One Unit Isn’t Enough
Generator paralleling links two or more units so they share the load as a single power source. A controller matches voltage, frequency and phase before it closes the connection.
Parallel generators make sense when:
- Your peak demand is much higher than your average demand
- Downtime costs you money and you need backup if one unit stops
- You move power between sites and two smaller units are easier to transport
- Your diesel generator often runs at light load, which causes wet stacking and carbon build-up
| Factor | One large genset | Parallel generators |
| Upfront cost | Often lower | Often higher |
| Fuel use at light load | Poorer | Better, as one unit can shut down |
| Backup if a unit fails | None | Remaining unit keeps running |
| Transport | Harder | Easier |
| Setup | Simple | Needs matched units and controls |
Only parallel units built for it. Inverter generators usually need a parallel kit and the same model on both sides. Larger diesel generator sets need synchronising controllers set up by a qualified technician.
Where a Generator’s Transfer Switch Fits In?
If your generator backs up a home, shed or business, you need a generator’s transfer switch. It isolates your building from the grid, so the genset can’t feed power back into the lines and put line workers at risk.
In Australia, AS/NZS 3010 covers connecting generating sets to electrical installations. A licensed electrician must install the switch.
- Manual transfer switch: You start the generator and flip the switch yourself. It suits farms and sheds with occasional outages.
- Automatic transfer switch (ATS): It senses a mains failure, starts the genset and moves the load across. Many ATS controllers bring loads on in stages, which eases the start-up surge.
For parallel generators on standby duty, the transfer switch and paralleling controls must work together. Plan both at the same time.
How Thornado Can Help?
Thornado supplies generators, pumps, hoses and fittings to farms, construction crews, mining contractors and homeowners across Australia. For start-up load problems, our diesel generator range is a practical place to start:
- 10kVA Silent Diesel Generator, Key Start, 3 Phase for sites running three-phase pumps and compressors
- 8.5kVA Silent Diesel Generator, Single Phase for workshops, farms and backup power
- Full diesel generator range
Why buy from Thornado:
- 12 months warranty on products
- 30 days money back
- Free delivery on orders over $200 ex GST
- Trade accounts for approved businesses
- Sizing advice from our team in Ingleburn, NSW
Not sure which genset suits your load?
Call (02) 9600 8883 or contact us with a list of your equipment, and we’ll help you size it.
Conclusion
A generator that loses power when several machines start usually needs better start-up planning, not replacement.
Stagger your loads, size for starting current and keep up the servicing.
When demand keeps growing, generator paralleling and a properly installed generator’s transfer switch give you more power and more reliability.